Description
Performance:
• With double conversion online design, zero output transfer time. Single phase input and output voltage.
• Adopt DSP digital control, excellent performance indicators, more steady and reliable.
• Adopt active power factor correction technology (PFC), the input power factor is 1, can reduced the pollution to the grid, To energy saving and reducing system investment.
• Ultra-wide input voltage range.
• Input frequency range 40~70Hz, support various fuel generators.
• With LCD+LED real-time display, users can intuitively understand the UPS operating status.
• With self- detection function, can detect hidden faults of UPS in time.
• With AC input over voltage, low voltage protection, output overload protection, short circuit protection, temperature protection, battery low voltage warning protection and battery overcharge protection.
• The efficiency of the whole UPS is as high as 95.5%, which reduces the power loss of it and saves the user’s use cost.
• When there is no mains power, you can directly use the battery to cold start.
• With input neutral and live line detection function, avoid the reverse connection of UPS utility input
• When utility cut-off, the UPS discharge battery in the battery mode; when the city power is recovery ,UPS turn on automatically,and charge battery at the same time, as unattended function.
• Standard RS232 communication outlet ,connect UPS and computer to realize multifunctional and multi-purpose monitoring and management operations, available SNMP card (optional) to UPS remote monitoring function.
Specification:
Model | H6KRS | H10KRS |
---|---|---|
Rated Capacity | 6KVA/6KW | 10KVA/10KW |
Input | ||
Input connection type | L+N+PE | |
Rated input voltage | 208/220/230/240VAC | |
Voltage range | 110-300VAC | |
Frequency rage | 50/60+HZ (default), ±10HZ (can be set) | |
Input power factor | ≥ 0.99 | |
Input THD | ≤ 4% % linear load | |
Output | ||
Output connection type | L+N+PE | |
Output voltage | 208/220/230/240VAC | |
Output accuracy | ±1% | |
Output frequency | Mains mode:same as AC frequency, battery mode : 50/60HZ+-0.1% | |
Output THD | ≤2% linear load, ≤ 4% Non-linear load (PF=0.7) | |
Output power factor | 1 | |
Overload Capacity | AC mode :
30min@102%~110% Load; 10min@110%~130% Load; 30s@130%~150% Load; 200ms@>150% Load Battery mode : 10min@102%~110% Load; 1min@110%~130% Load; 10s@130%~150% Load; 200ms@>150% Load |
|
Transfer time | ||
AC mode switch to battery mode | 0ms | |
mains inverter mode switch to bypass mode | 4ms | |
AC priority mode | Support | |
Overall Efficiency | ||
AC Mode (Full Load) | Peak efficiency 95.5%, Full load efficiency 95% | |
Battery Mode (Full Load) | Peak efficiency 95.3%, Full load efficiency 94.8% (20pcs Battery) | |
Battery | ||
Battery type | Lead Acid Battery | |
Number of batteries | / | |
Battery Charge Current | 1-12A (can be set) 1A (default) | |
Charging Mode | Two-stage/three-stage charging | |
Display | ||
LCD | 2×8 PIN/Pitch 2.54mm, support 128-bit segment code, up to 4 buttons + 4 LEDs, can display operating mode / load / input / output, etc | |
Interface | ||
RS-232 | Support: Windwos 2000/2003/XP/Vista/2008/7/Linux/Unix and MAC | |
USB | Windows Famlly & MAC | |
Intelligent slot (Optional) | SNMP/AS400 Relay Card/RS485 | |
Environmental parameters | ||
Operating ambient temperature | 0~40℃ | |
Operating environment humidity | 20%~95% (No condensation) | |
Storage temperature | -15~60℃ ( Battery : 0~40℃ ) | |
Altitude | The altitude should not exceed 1000m, derating above1000m, up to 4000m (max ) , refer IEC62040 | |
Noise | ≤45db | |
Mechanical Specifications | ||
Dimensions (D*W*H) (mm) | 438*420*88 | |
Net weight (kg) | 10
(without battery pack) |
11
(without battery pack) |